光伏发电接入弱电网电能质量治理研究
刘峪涵, 贺鑫, 罗隆福

Study on Power Quality Control of Photovoltaic Power Generation Connected to Weak Power Grid
LIU Yuhan, HE Xin, LUO Longfu
表4 60 kV并网点高频电压畸变率
频次 THD(%) 抑制率
(%)
国际
标准(%)
滤波前 滤波后
11th 0.45 0.22 51.1 1.50
13th 0.39 0.13 66.7 1.50
17th 0.30 0.06 80 1
19th 0.29 0.04 86.20 1
21th 0 0 0 0.70
23th 2.56 0.29 88.70 0.70
25th 4.17 0.41 90.20 0.70
26th 1.25 0.12 90.40 0.68