低风压导线与常规导线对比分析
|
|
段旭东,韩宇,陆春阳,姜然凇
|
Comparative Analysis of Low Wind Pressure Conductor and Conventional Conductor
|
|
Xudong DUAN,Yu HAN,Chunyang LU,Ransong JIANG
|
|
表4 电能损耗计算
|
| |
|
导线 型号 | 输送容量/MW | 导线输送电流/A | 运行温度/℃ | 交流 电阻 /(Ω/km) | 电阻 功率/(kW/km) | 电阻损耗 /(MW·h/km) | | 3 000 h | 4 000 h | 5 000 h | | 导线2 | 1 000 | 303.9 | 53.5 | 0.086 14 | 95.4 | 286.3 | 381.8 | 477.2 | | 导线1 | 1 000 | 303.9 | 52.9 | 0.079 16 | 87.7 | 263.1 | 350.9 | 438.6 |
|
|
|