基于灵敏度法的停电系统网架重构过程中负荷调整策略
石屹岭,马福龙,周前,汪成根,陈晞

Load Adjustment Strategy Based on Sensitivity Analysis During Network Reconfiguration of Blackout System
Yiling Shi,Fulong Ma,Qian Zhou,Chenggen Wang,Xi Chen
表3 电压越限调整后的潮流计算结果
Tab.3 Results of power flow calculation after regulating the over-limit voltage
节点
编号
电压
(pu)
发电有功
/MW
发电无功
/Mvar
负荷有功
/MW
负荷无功
/ Mvar
无功补偿
/ Mvar
4 1.0500 0 0 147.9 54.4 0
5 1.0570 0 0 0 0 0
6 1.0580 0 0 0 0 0
10 1.0570 0 0 0 0 0
11 1.0580 0 0 0 0 0
14 1.0510 0 0 0 0 0
15 1.0470 0 0 126.6 60.60 0
16 1.0490 0 0 79.5 7.8 0
19 1.0520 0 0 0 0 0
31 1.0000 290.7 0 9.2 4.6 58.3
32 0.9830 97.5 -24.9 12.5 0 0
33 0.9830 0 0 10 0 0