一批油浸倒置式电流互感器故障分析及改进措施
|
|
吴玉硕,胡春江,彭鹏,张晓玲,温定筠,王晓飞
|
Fault Analysis and Improvement Measures of Oil Immersed Inverted Current Transformer
|
|
Wu Yushuo,Hu Chunjiang,Pen Peng,Zhang Xiaolin,Wen Dingjun,Wang Xiaofei
|
|
表3 电容量及介质损耗测量数据
|
Tab.3 Test data of capacity and dielectric loss
|
|
| (a)第一次:局部放电后介质损耗测量,电压(10~210)kV | | 电压/kV | 10 | 50 | 80 | 110 | 140 | 180 | 210 | | CX/pF | 804.42 | 804.44 | 804.46 | 804.49 | 804.53 | 804.95 | 805.17 | | tanδ(%) | 0.243 | 0.251 | 0.256 | 0.26 | 0.263 | 0.305 | 0.32 | | (b)第二次:局部放电后介质损耗测量,电压(10~210)kV | | 电压/kV | 10 | 50 | 80 | 110 | 140 | 180 | 210 | | CX/pF | 804.41 | 804.42 | 804.44 | 804.47 | 804.64 | 805.25 | 805.62 | | tanδ(%) | 0.244 | 0.252 | 0.253 | 0.26 | 0.264 | 0.315 | 0.324 | | (c)第三次:历时3h局部放电监测后复测电容量及介质损耗,电压(10~210)kV | | 电压/kV | 10 | 50 | 100 | 110 | 150 | 190 | 210 | | CX/pF | 802.57 | 802.59 | 802.85 | 803.57 | 806.15 | 808.1 | 809.08 | | tanδ(%) | 0.246 | 0.255 | 0.29 | 0.39 | 0.613 | 0.692 | 0.723 | | (d)第四次:1.2Um/kV电压下1h局部放电监测后复试电容量及介质损耗,电压(10~210)kV | | 电压/kV | 10 | 50 | 110 | 130 | 170 | 190 | 210 | | CX/pF | 802.15 | 802.2 | 804.45 | 806.38 | 809.58 | 810.68 | 811.7 | | tanδ(%) | 0.271 | 0.296 | 0.625 | 0.822 | 0.96 | 0.983 | 0.997 |
|
|
|