750kV输电线路风偏跳闸原因分析及改造措施研究
杨肖辉,张东,李晓光,董新胜,张振泉,陈艳超

Analysis and Reform Measures of 750kV Transmission Line Wind Biased Tripped
Yang Xiaohui,Zhang Dong,Li Xiaoguang,Dong Xinsheng,Zhang Zhengquan,Chen Yanchao
表1 ZB231P型杆塔导线风偏时电气间隙距离与风偏角关系(以40m塔高)
Tab.1 ZB231P-type tower wire wind deviation when the electrical clearance distance and wind angleRelationship (40m heighttower)
距横担距离/m 风偏角/(°)
2.615 0 56
2.495 7 57
2.375 6 58
2.254 9 59
2.133 4 60
2.011 3 61
1.888 6 62
1.765 3 63
1.641 4 64